How the cable is selected
A cable has to pass three independent checks. The recommended size is the smallest standard size that passes all of them, and the result tells you which check decided it.
- Ampacity. The tabulated current rating is multiplied by the temperature, grouping and soil correction factors. The result must be at least the design current, and at least the protective device rating if you enter one.
- Voltage drop. DC:
2 × L × R × I. AC:k × L × I × (R cosφ + X sinφ)with k = 2 for single-phase and 1.732 for three-phase. R is taken at the conductor's maximum operating temperature unless you choose 20 °C. - Short-circuit withstand. Minimum area
S = I × √t ÷ k, with k = 143 (copper XLPE), 115 (copper PVC), 94 (aluminum XLPE), 76 (aluminum PVC).
Solar and battery circuits
For PV source and output circuits, NEC 690.8 sizes conductors at 125% of the 125% Isc value, which is the 1.56 design factor above. Battery and low-voltage DC runs are usually decided by voltage drop rather than ampacity, so the result tells you which one governs.
Data sources
IEC ampacities are the values of IEC 60364-5-52 Tables B.52.2 to B.52.13 as published in manufacturer technical data (EUPEN, Technical Data for LV Power and Control Cable 0.6/1 kV, 2022), together with the correction factors of Tables B.52.14 to B.52.21. Conductor resistances are IEC 60228 class 2 values from the same document. NEC ampacities follow Table 310.16 with the temperature correction of 310.15(B)(1) and the adjustment factors of 310.15(C)(1).
The Pakistan market options use manufacturer catalogues. "Pakistan Cables" is one menu entry covering nine underlying tables from two catalogues: the General Wiring book (BS 7671 Tables 12 and 14, PVC copper, small multi-core sizes) and the 2026 Low Voltage Cables Catalogue (Tables 4D1/4D3, 4H1/4H4, 4E2/4E4 and 4J1/4J4 — PVC 70 °C and XLPE 90 °C, copper and aluminium, single- and multi-core, unarmoured and SWA/AWA-armoured). Choosing a conductor, insulation, core type (single/multi-core) and armour in the form picks the matching table automatically; each one's ampacity, resistance and reactance come directly from its own table and installation arrangement (clipped/touching, free-air/trefoil, spaced, or direct-buried), not a shared formula. A combination the catalogues don't cover (for example copper, PVC, multi-core, armoured) shows a plain message rather than a guess. "Fast Cables" covers the armoured XLPE direct-buried ratings. Solar PV cable data comes from Fast Cables, Pakistan Cables (4 mm² TDS) and Leader Technology (4 mm² datasheet): all three agree at 55 A / 5.09 Ω/km for 4 mm² (Leader's 4.75 Ω/km is lower, so the higher figure is used), and the Pakistan Cables PCL Solar catalogue's own installation-method ratings (free air / on a surface / two touching) and ambient-correction table cover 1.5–240 mm². The Pakistan Cables catalogue's temperature correction tables are numerically identical to the IEC values used above, and its soil-resistivity table was used to confirm, rather than replace, the existing direct-buried soil factors. Full extraction notes, including two misprinted catalogue cells that were corrected by interpolation, are in extraction/REVIEW.md and extraction/CROSSCHECK.md alongside this file.
What this tool does not cover
- Cables in thermal insulation (methods A1 and A2), buried cable groups with wider spacing, and multi-layer groups.
- Harmonic currents, neutral loading, parallel conductors per phase. If no listed size passes, consider parallel conductors per phase — this tool does not size them.
- NEC rules such as the next-size-up overcurrent provision in 240.4(B), and ampacities for specific manufacturer constructions that differ from the standard tables.
- Pakistan Cables' flexible cords, and 10 further Fast Cables low-voltage cable families (unarmoured XLPE/PVC standard, halogen-free variants, fire-resistant/MICA, screened, concentric-neutral, overhead aerial) that were located in the catalogue but not yet digitized into this tool.
- The Fast Cables medium-voltage, bare-conductor, and WAPDA-specification-conductor ranges.
- Method B (conduit) for the new single-core aluminium XLPE source (4J1): the catalogue page prints a reactance value for one size that is clearly a misprint, so that arrangement is not offered until it can be checked against a physical copy.
- AWG conductor resistance is derived from conductor area, so it can differ slightly from NEC Chapter 9 Table 8.
